An Outbreak of Legionnaires Disease Caused by Long‐Distance Spread from an Industrial Air Scrubber in Sarpsborg, Norway

Karin Nygård, Øyvind Werner-Johansen, Svein Rønsen, Dominique A. Caugant, Øystein Simonsen, Anita Kanestrøm, Eirik Ask, Jetmund Ringstad, Rune Ødegård, Tore Jensen, Truls Krogh, E. Arne Høiby, Eivind Ragnhildstveit, Ingeborg S. Aaberge and Preben Aavitsland

in Clinical Infectious Diseases

Published on behalf of Infectious Diseases Society of America

Volume 46, issue 1, pages 61-69
Published in print January 2008 | ISSN: 1058-4838
Published online January 2008 | e-ISSN: 1537-6591 | DOI: http://dx.doi.org/10.1086/524016
An Outbreak of Legionnaires Disease Caused by Long‐Distance Spread from an Industrial Air Scrubber in Sarpsborg, Norway

More Like This

Show all results sharing these subjects:

  • Infectious Diseases
  • Immunology
  • Public Health and Epidemiology
  • Microbiology

GO

Show Summary Details

Preview

Background. On 21 May 2005, the Norwegian health authorities were alerted by officials from a local hospital that several recent patients had received the diagnosis of legionnaires disease; all patients resided in 2 neighboring municipalities. We investigated the outbreak to identify the source and to implement control measures.

Methods. We interviewed all surviving case patients and investigated and harvested samples from 23 businesses with cooling towers and other potential infection sources. The locations of the businesses and the patients' residences and movements were mapped. We calculated attack rates and risk ratios among people living within various radii of each potential source. Isolates of Legionella pneumophila were compared using molecular methods.

Results. Among 56 case patients, 10 died. The case patients became ill 12–25 May, resided up to 20 km apart, and had not visited places in common. Those living up to 1 km from a particular air scrubber had the highest risk ratio, and only for this source did the risk ratio decrease as the radius widened. Genetically identical L. pneumophila serogroup 1 isolates were recovered from patients and the air scrubber. The air scrubber is an industrial pollution‐control device that cleans air for dust particles by spraying with water. The circulating water had a high organic content, pH of 8–9, and temperature of 40°C. The air was expelled at 20 m/s and contained a high amount of aerosolized water.

Conclusions. The high velocity, large drift, and high humidity in the air scrubber may have contributed to the wide spread of Legionella species, probably for >10 km. The risk of Legionella spread from air scrubbers should be assessed.